6-7SectionSetting Conditions for Communications with Host by Using Memory Switches
166
Display the data bits to be set (7 bits or 8 bits)
by pressing the Data Bit Length touch switch.
Display the stop bits to be set (1 bit or 2 bits)
by pressing the Stop Bit Length touch switch.
Display the parity to be set (None, even, odd)
by pressing the Parity Bit touch switch.
Display the communication speed to be set
(1200, 2400, 4800, 9600, 19200, 38400 bps.)
by pressing the Comm. Speed touch switch.
Display the condition of the flow control to be
set (None, RS/CS, XON/XOFF) by pressing
Flow Control touch switch.
If the RS-422A is selected for serial port B set-
ting, RS/CS is not displayed.
Display presence or absence of the response
by pressing the Response touch switch.
The setting option changes each time the
touch switch is pressed.
In this example, serial port A is used.
Press the Quit touch switch.
To quit the communications speed setting screen without setting the commu-
nications speed, press the Abort touch switch. The NT31/NT31C returns to the
memory switch setting screen (4/4) and the previous communications speed
remains in effect.
On completion of communications speed setting, the NT31/NT31C returns to
the memory switch setting screen (4/4).
To set other memory switches, select the relevant screen using the [
] (next
screen) or [
] (previous screen) touch switch, then make the setting.
To confirm the settings and quit the memory switch setting screen, press the
Quit touch switch. The settings made last will be set and the NT31/NT31C will
return to the MAINTENANCE MODE MENU screen.
To quit the memory switch setting screen without confirming the settings, press
the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE
MODE MENU screen with the previous settings still in effect.