275
Adjusting the Communications Load Section 10-2
a. Click the Close Button at the bottom of the Usage of Device Bandwidth
Dialog Box.
b. Double-click the device that is set as the originator of the desired con-
nection. The Edit Device Parameters Dialog Box will be displayed.
c. In the Register Device List, select the connection for which you want
to change the RPI, and click the Edit Button.
d. The device’s Edit Connections Dialog Box will be displayed. Input a
new RPI value, and click the OK Button.