Omron SYSMAC CJ1W-EIP21 Manual de usuario Pagina 174

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 464
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 173
148
Setting Tag Data Links Section 6-2
Example 2: Automatic Connections with the Ellipses
The following connections would automatically be set if there is an output tag
set named O_Signal at node A and input tag sets named I_Signal at nodes B
and C, and “O_” and “I_” were set as ellipses.
1,2,3... 1. Set the same tag set names for the output and input tag sets for the con-
nection. The tag set names can also include forward and backward el-
lipses.
2. Select Auto Connection from the Network Menu. The connections will be
set automatically.
A dialog box will appear to set forward and backward ellipses for both out-
put (product) and input (consume) tag sets as soon as automatic connec-
tion setting processing has begun.
Input the ellipses and click the OK Button. Automatic setting will be pro-
cessed.
3. If there are tag sets that meet the conditions for automatic connection set-
ting, they will be displayed.
Connection
EtherNet/IP
Node A
Node B Node C
Connection
Output tag set: O_Signal
Input tag set: I_Signal
Input tag set: I_Signal
Excluded characters: O_ and I_
Vista de pagina 173
1 2 ... 169 170 171 172 173 174 175 176 177 178 179 ... 463 464

Comentarios a estos manuales

Lynwood 14 Mar 2024 | 16:50:43

How To Create An Awesome Instagram Video About Pornstars On Adultwork British Porn Stars Xxx (Https://Qooh.Me)